The quality of electrical insulation is a decisive factor for functional capability and service life of electric motors, generators and other electrical rotating equipments.
The quality of electrical insulation is a decisive factor for functional capability and service life of electric motors, generators and other electrical rotating equipments.
Three way insulation consists of a polyester film with N-ARAMID paper glued on both sides with high temperature adhesives. This composite (Flexible) material has special importance insulating class F electrical machines. N-ARAMID paper has outstanding thermal characteristics and extra ordinary resistance against chemicals and solvent.
The better electrical and mechanical properties of polyester sheet are ideally complemented by high temperature resistance of the N-ARAMID paper. Two sided covering of the Polyester film with N-ARAMID paper, protects these laminates against influences of hydrolysis, making these laminates an importance insulation component in manufacturing insulating class Felectrical equipments.
Advantages of GAR-FLEX (APA) Class F Laminates (155°C)
High chemical and solvent resistance
Suitable for automatic Insertion
Laminates have good dielectric strength
Protects from influence of hydrolysis
High temperature resistance
Good mechanical properties
| SI No. | Product Name | Composite | Application |
|---|---|---|---|
| 1 | GAR-FLEX® | GAR-FLEX® + Polyester Film + N-ARAMID | For Moter & Generators: Slpt insulation / closers Phase insulation / interlayers insulation / core insulation For Transformers: Layers, core & cover insulation conductor insulations For Choke coils: Conductor & shaded components |
| Property | Clause in IEC 626-2 | Unit Tolerance | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Laminate Nominal Thikness | 2 | mm | 0.14 | 0.15 | 0.17 | 0.19 | 0.22 | 0.24 | 0.31 | 0.37 | 0.47 |
| Laminate Nominal Tolerance | 2 | ± % | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 10 | 10 |